Technical data CX1100-0003

Technical data CX1100-0003 1:

Technical  data

CX1100-0003

Power supply

24 VDC (-15%/+20%) To meet the UL requirements use a 4 A fuse or a power supply that has to satisfy NEC class 2!

Technical data CX1100-0003 2:

Dielectric strength

500 Veff (supply / internal electronics)

Max. power consumption

4 W

Recommended fuse at 24 V

4 A

K-bus connection

yes (adapter terminal)

E-bus connection

-

IP-Link connection

yes

K-bus power supply to

1.75 A

connection type

Cage-Clamp (adapter terminal)

NOVRAM

8 kByte

Display

FSTN display 2 lines x 16 characters of text, illuminated

I/O-DPRAM

4 kByte

Diagnose LED

1 x PWR, 1 x I/O Run, 1 x 1/O Err

Dimensions (W x H x D)

58 mm x 100 mm x 91 mm

weight

app.350 g

operating/storage temperature

0° C ... +55° C / -25° C ... +85° C

Relative humidity

95% no condensation

Vibration/shock resistance

conforms to  EN 60068-2-6 / EN 60068-2-27/29

EMC resistance burst / ESD

conforms to EN 61000-6-2 / EN 61000-6-4

protection class

IP 20