Power supply (X102)
To supply the CU81x0 UPS, two 9-pin connectors with push-in connection are used. For the 9-pin connectors, cables with a cross-section of 0.5 mm² to 1.5 mm² or AWG20 to AWG16 are required. With cable end sleeve max. 1 mm2 or AWG 17 are permissible.
No. | Pin | Description |
---|---|---|
1 | Uin, | +24 V DC input, power supply for UPS. |
2 | U1out, | +24 V DC UPS output with UPS-OCT support, interface for the device being supported. |
3 | U2out, | +24 V DC UPS output, interface for a second device being supported e.g. control panel (display). |
The U1out and U2out interfaces together must not exceed the maximum output current of the UPS.
No. | Pin | Description |
---|---|---|
4 | UPS RDY, | +24 V DC output. This output is switched to 24V when the UPS charging is above a set threshold (e.g. 80 %). |
5 | P FAIL, | +24 V DC output for power-fail-signal. This output is switched to 24 V if the power supply fails or if P SHDN is activated. This output can be connected with the PC_ON input on a Beckhoff Industrial PC or any PLC input. |
6 | NC | Reserved. |
7 | UPS EN | +24 V DC input. A falling edge from 24 V to 0 V signals the UPS to switch off the outputs U1out and U2out immediately. This input can be connected with the PC_STATUS output on a Beckhoff Industrial PC or any PLC output. |
8 | P SHDN | +24 V DC input. A rising edge from 0V to 24V at this input triggers an immediate shutdown of the operating system. If there is 24 V at P_SHDN on startup, the PC will first be started with a falling edge from 24 V to 0 V. |