Connection via UPS-OCT

A special feature of the Beckhoff CU8110-0120 UPS is UPS-OCT (One Cable Technology) as a communication technology between UPS and industrial PC. The two connecting cables (+24 V, 0 V) between the industrial PC and the UPS are used simultaneously for the power supply of the industrial PC and for bidirectional, modulated data transmission. This means that supply and communication are realized via a single cable.

System requirements for UPS-OCT.

UPS module

Hardware version

CU8110-0120

1.5

Only the U1out interface of the UPS supports UPS-OCT communication. If you want to use UPS-OCT technology, the industrial PC used must also be UPS OCT-capable.

Special features of UPS-OCT wiring

For UPS-OCT, a special shielded power cable of type C9900-K90x is required. Cable lengths of up to 10 m are supported. The cable shield must be properly connected on both sides:

Special features of the industrial PC:

Notice

Communication errors and malfunctions

Simultaneous use of UPS-OCT and the PC-ON input on the industrial PC can lead to unpredictable malfunctioning of the UPS and the connected PC.

  • In UPS-OCT mode, the PC-ON input on the voltage socket of the industrial PC must not be used.
Connection via UPS-OCT 1:Fig.13: Connection example via UPS-OCT with a CU8110-0120 UPS and a C6015 Industrial PC.

Special features embedded PC (CX series):

Connection via UPS-OCT 2:Fig.14: Connection example via UPS-OCT with a CU8110-0120 UPS and a CX5240 Embedded PC.

Status display

An active UPS-OCT connection is both displayed in the Beckhoff UPS software and signaled via a green status LED on the CX and IPC side.