Holding times
Discharge current [A] | Time to switch-off [s] | Usable energy [Wh] |
|---|---|---|
0.5 | 280 | 0.93 |
1 | 145 | 0.97 |
1.5 | 95 | 0.95 |
2 | 70 | 0.93 |
2.5 | 55 | 0.92 |
3 | 45 | 0.90 |
3.5 | 35 | 0.82 |
4 | 30 | 0.80 |
4.5 | 25 | 0.75 |
5 | 20 | 0.67 |
Discharge current [A] | Time to switch-off [s] | Usable energy [Wh] |
|---|---|---|
0.5 | 280 | 0.93 |
1 | 145 | 0.97 |
1.5 | 95 | 0.95 |
2 | 70 | 0.93 |
2.5 | 55 | 0.92 |
3 | 45 | 0.90 |
3.5 | 35 | 0.82 |
4 | 30 | 0.80 |
4.5 | 25 | 0.75 |
5 | 20 | 0.67 |