Technical data

Technical data

Product designation

CP6706-0001

Weight

CP6706-0001: 1.75 kg

Supply voltage

22-30 VDC (24 V DC power supply)

Power consumption

Data sheet for power consumption and power loss in the download finder:

https://www.beckhoff.com/en-en/support/download-finder/search-result/?download_group=691754572

Secure element

CP6706-0001-0050: fTPM 2.0 not enabled

CP6706-0001-0060: fTPM 2.0 enabled

CP6706-0001-0070: fTPM 2.0 enabled

(see TPM documentation)

Standard protection rating/
Stainless steel protection rating

Front IP54, rear IP20/
Front IP65, rear IP20

Vibration resistance (sinusoidal vibration)

EN 60068-2-6:

10 ... 58 Hz:

0.035 mm

58 ... 500 Hz:

0.5 G (~ 5 m/ s2)

Shock resistance (shock)

EN 60068-2-27:

5 G (~ 50 m/s2), duration: 30 ms

EMC interference immunity

conforms to EN 61000-6-2

EMC interference emission

conforms to EN 61000-6-4

Permissible ambient temperature

Operation: 0 °C ... +50 °C

Transport/storage: -20 °C ... +65 °C

Permissible relative air humidity

Maximum 95%, no condensation

Transport and storage