Optional interfaces

You can extend the Panel PC beyond the basic configuration by additional interfaces. The following ordering options are available:

Ordering options interfaces

Options

Description

C9900-E185

IP65 connector in the connection compartment for the second on-board Ethernet adapter, push-pull Ethernet socket

C9900-B416

Third on-board Ethernet adapter on the 3½-inch motherboard for Intel Atom®, led out as IP65 built-in push-pull Ethernet socket 100/1000BASE-T on the connector bracket in the connection compartment

C9900-E186

IP65 connector M12 socket in the connection compartment for a serial interface RS232

C9900-E248

IP65 connector M12 socket in the connection compartment for a serial interface RS422, electrical isolation, overvoltage protection. Configuration as full duplex endpoint: Echo on, Auto send off, Always send on, Auto receive off, Always receive on, Termination on

C9900-E261

IP65 connector M12 socket in the connection compartment for a serial interface ES485, electrical isolation, overvoltage protection. Configuration as endpoint without echo: Echo off, Auto send on, Always send off, Auto receive on, Always receive off, Termination on

C9900-E283

IP65 connector in connection compartment for one USB 3.0 port, push-pull USB 3.0 socket

C9900-E304

USB-A socket in the connection compartment for a USB 3.0 port, with IP65 cover

C9900-E190

USB-A socket in the connection compartment for a USB 2.0 port, with IP65 cover

C9900-E329

1-port USB 2.0 socket behind the CFast/HDD/SSD flap of the CP32xx-1600-00x0 or CP37xx-1600-00x0 for a TwinCAT license key USB stick C9900-L100 or C9900-L101

The panel PC can be equipped with a maximum of six interfaces. No further interfaces can be ordered. Any interfaces that are ordered are installed ex factory.

The optional USB interface C9900-E329 is not located in the connection compartment, but behind the side cover near the motherboard battery and the storage medium. You can access the interface by removing the four M3 screws on the cover and then removing the cover.

Optional interfaces 1:Fig.8: Access USB interface

The position of the interface is suitable for the use of a license key USB stick. It is equipped with a local data memory for saving TwinCAT 3.1 license files. The stick is not included in the USB interface ordering option.

Optional interfaces 2:Fig.9: License key USB stick