Replacing the battery
  | |
Incorrect battery type Using a different type of battery can lead to a fire or explosion. 
  | 
  | |
Incorrect handling of the battery Handling the motherboard battery incorrectly can cause an explosion. 
  | 
Notice  | |
Failure of the electronics due to mechanical damage Scratches or damaged components on PCBs can cause the electronics to fail. 
  | 
The device does not contain a lithium-ion battery. The motherboard battery is a CR2032 lithium-metal cell. It is used to supply power to the clock integrated on the motherboard. If the battery is depleted or missing, the date and time are displayed incorrectly.
Battery type  | Electrical properties (at 20 °C)  | Dimensions  | |||
|---|---|---|---|---|---|
Nominal voltage  | Nominal capacity  | Diameter  | Height  | Weight  | |
CR2032  | 3.0 V  | 225 mAh  | 20.0 mm  | 3.20 mm  | 3.1 g  | 
Chapter 7.2 Maintenance shows where the battery is located.
To replace the battery, follow the steps below as shown in Figure 27:
- 1. Loosen and remove the M4 screw and the cover (section A).
 - 2. Pull the battery out of the panel PC with needle-nose pliers (section B).
 - 3. Insert the new battery into the PC by hand. Pay attention to the correct polarity. The negative pole of the battery must face the display.
 
Battery disposal
To dispose of the battery, remove it, tape off the poles and put it in the battery disposal.