cp-link3

Using the CPx8xx USB Bus Coupler

Bus Couplers of type CPx8xx are integrated into Beckhoff Panel PCs. Various different I/O terminals are connected through these Bus Couplers. In addition to the standard I/O channels of a Panel PC, further I/O terminals can be connected through which, for instance, special keys, LEDs, rotary switches or similar items can be operated. When a Panel PC is used as a CP Link 3 client there are different options for accessing the client's integrated USB Bus Coupler from the host PC:

▪
Using via the CP-Link 3 Virtual USB hub
▪
Access via "Virtual USB interface (Remote)"
–
via standard Ethernet
–
via RT Ethernet
▪
Access via network variables (RT Ethernet)
▪
Access via ADS to task or PLC variables linked to the local client
–
via standard Ethernet
–
via RT Ethernet


The differences between the different varieties is explained in the following table:

 
Bus Coupler logically connected with
I/O access from
RT Ethernet
Configuration effort
Release of outputs possible (see explanation underneath the table)
 
Host PC
Client PC
Host PC
Client PC
1
X
 
X
 
 
low
Yes
2.a
 
X
X
 
 
low-medium
Yes
2.b
 
X
X
 
X
medium
No
3
 
X
 
X
X
medium-high
No
4.a
 
X
 
X
 
high
No
4.b
 
X
 
X
X
high
No
 

Possible release of the USB Bus Coupler outputs:

The USB Bus Coupler built-in to the client expects a certain time interval, in which it receives data to write to its outputs. In the standard configuration of a CPx8xxx Bus Coupler this time interval is 100 ms. If this time interval cannot be met, the outputs of the Bus Coupler are released. Depending on the usage type of the USB Bus Coupler, in practice under certain conditions, the time interval may not be met and the outputs of the Bus Coupler released. Generally, this seldom if ever happens, but cannot be ruled out altogether. Reasons for this are the type of network connection of the Bus Coupler integrated into the client to the host PC or the operating system architecture of the host PC. If the I/O access of the host PC takes place via a standard Ethernet connection, during data exchange with the Bus Coupler, a lot of small data packets per cycle must be sent consecutively over the IP connection. Depending on the network load and the client CPU load sending of these packets can take longer than the time interval defined.
To be certain that these outputs are not released under any circumstances, I/O access from the host must be implemented by RT Ethernet, or the I/O access must take place on the client PC itself. If I/O access takes place on the client itself this does however increase the configuration effort as the inputs and outputs of the Bus Coupler cannot be used directly on the host PC, but must be made available by ADS or network variables.

CP Link 3 and RT Ethernet
If the same network adapter is used for CP Link 3 as for RT Ethernet, RT Ethernet affects the data throughput of CP Link 3. Depending on cycle time of the real-time task this effect can be so large that the performance of CP Link 3 is substantially reduced. Furthermore, when using CP Link 3 via RT Ethernet adapter under certain conditions it can lead to connection losses (see chapter on Comments, or alternatively Help with faults). In addition, TCP/IP must be selected as transfer protocol for graphic data, since the RT Ethernet adapters of the clients do not accept UDP multicast packages (See also Client configuration). In some cases it may therefore be advisable to use a separate network adapter for RT Ethernet.
 

Cycle time for the data exchange with the Bus Coupler

The recommended cycle time for the data exchange with the terminals of a USB Bus Coupler is 50 to 80 milliseconds. The following options are available for ensuring compliance of the cycle time during data exchange with the Bus Coupler:

▪
Tasks with variables that are linked with the I/O channels of the Bus Coupler are configured with a cycle time of more than 50 milliseconds.
▪
Tasks with variables that are linked with the I/O channels of the Bus Coupler may be configured with a cycle time of less than 50 milliseconds, although in this case it is necessary to activate the so-called Async Mode for the Bus Coupler:
 
Additional information
•
Using via the CP-Link 3 Virtual USB hub
•
Access via "Virtual USB interface (Remote)"
•
Access via network variables
•
Access via ADS to task or PLC variables linked to the local client
Also see about this
•
Configuration of RT Ethernet devices