EtherCAT P

The industrial PC has an EtherCAT P interface (X101). EtherCAT P (EtherCAT + Power) is an extension of the EtherCAT technology in the area of cabling. Via the connector in IP65/67 design, you can use the four-wire Ethernet cable (according to IP65) for data and for two electrically isolated, individually switchable 24 V/3 A supplies. This allows you to cascade several EtherCAT devices. For connection and power supply of I/O as well as field devices you only need one cable. Beckhoff recommends the use of the following cable:

Alternatively, you can use other cables whose length exceeds 20 cm.

A protective cap for the EtherCAT P interface is included in the scope of delivery.

EtherCAT P 1:Fig.2: EtherCAT P interface pin numbering
EtherCAT P interface pin assignment

Pin

Signal

Description

1

Tx +

LAN signal + and GNDS

2

Rx +

LAN signal + and GNDP

3

Rx -

LAN signal and peripheral voltage 24 V (UP)

4

Tx -

LAN signal and control voltage 24 V (US)

On the housing of the PC there are the three LEDs of the EtherCAT P interface (see Fig. 3). They provide information about the Link Activity (EC L/A), the system voltage (ECP US) and the peripheral voltage (ECP UP).

EtherCAT P 2:Fig.3: EtherCAT P LEDs

The following table shows the meaning of the colors and flashing intervals:

LEDs EtherCAT P interface

LED

Color/flashing interval

Meaning

EC L/A

yellow on

yellow flashing

Connection to network

Data transmission in progress

ECP US

green on

red on

Voltage in normal range

Voltage outside the normal range

ECP UP

green on

red on

Voltage in normal range

Voltage outside the normal range

You can use the Beckhoff Device Manager to switch the system voltage US and the peripheral voltage UP. For more information, refer to Chapter 5 Beckhoff Device Manager.