Installation in the control cabinet
Notice | |
Extreme environmental conditions Extreme environmental conditions can cause damage to the device.
|
Notice | |
Incorrect installation Incorrect installation in a control cabinet prevents air circulation in the device and causes impaired functioning.
|
The device is designed for installation inside a control cabinet in machine and system engineering. The environmental conditions specified for operation must be observed.
Only install the device in the control cabinet with the power supply facing upwards.
With the standard mounting plate, you can mount the industrial PC in the control cabinet via the rear panel (see Chapter 4.2.2 Installation in the control cabinet). The industrial PC is automatically delivered with the mounting plate already mounted (see fig. 9).