Power supply
In its basic configuration, the industrial PC is equipped with a 100-240 V AC, 50-60 Hz full range power supply unit.
The following table lists the maximum current carrying capacity of the 100–240 V AC power supply:
Output voltages power supply unit | Current load 100-240 V AC power supply unit max. |
|---|---|
+3.3 V | 20 A |
+5 V | 20 A |
+12 Total | 45.5 A |
-12 V | 0.3 A |
+5 V stand by | 2.5 A |
The total power output of the +3.3 V and +5 V lines must not exceed 100 W. The maximum total current for the +12 V outputs must not exceed 50 A.
The power supply is connected via the IEC socket (X101) on the top of the industrial PC. The assignment includes a protective conductor (1), a neutral conductor (2) and an outer conductor (2).
Optionally, you can order the industrial PC with a 24 V DC power supply unit. In this case, the industrial PC is supplied with a nominal voltage of 24 V. A 3-pin socket is used for the connection of the power supply (X101) as well as the external wiring (X102) of the industrial PC.
The main supply voltage is applied between PIN 1 (24 V) and PIN 3 (0 V) of the voltage socket (X101).
Pin | Signal | Description |
|---|---|---|
1 | +24 V | 24 V supply voltage, positive pole |
2 | Protective earth | |
3 | - | 24 V supply voltage, negative pole |
The positive pole of the supply voltage at PIN 1 of the voltage socket (X101) is looped through to PIN 3 of the socket (X102). PIN 3 thus serves as the positive pole for PC-ON.
Pin | Signal | Description |
|---|---|---|
1 | P-S | Output power status, minus is the negative pole of the power supply (X101) |
2 | PC-ON | Input PC-ON |
3 | +24 V | Supply voltage and positive pole for PC-ON |
The plug for the power supply can accommodate wire cross-sections of up to 4 mm2. The plug for the external wiring can accommodate wire cross-sections of up to 1,5 mm2. For long supply lines, use 4 mm2 or 1,5 mm2 cables to achieve a low voltage drop on the supply lines. There should be at least 22 V at the power supply plug of the device, so that the device remains switched on during voltage fluctuations. The plugs are included in the delivery. You can obtain replacement plugs from your Beckhoff Sales using the following ordering options:
- C9900-P962: Plug for power supply
- C9900-922: Plug for external wiring