Assembly of the supply cable
Install the cable for the power supply of the device using the material supplied for connector assembly. It consists of an 8-pin connection strip and a strain relief housing with cable tie.
Assembly of the supply cable
First mount the plug on the cable as follows:
- 1. Remove the insulation from the cable ends (8-9 mm).
- 2. Screw the cable ends into the connection strip. For the pin assignment of the connector, see Chapter Power supply.
- You have fitted the supply cable to the plug.
Assembly of strain relief housing
Now mount the strain relief housing on the previously connected plug and supply cable:
- 1. Thread the cable tie into the lower part of the strain relief housing (section A).
- 2. Insert the connection strip into the lower part of the strain relief housing (section B).
- 3. Tighten the cable tie and remove the plastic tab (section C).
- 4. Attach the upper part of the strain relief housing by snapping it onto the lower part (section D).
- You have mounted the strain relief housing.
To remove the strain relief housing, proceed as follows:
- 1. Use your fingers to bend the latching lugs on the lower part slightly outwards.
- 2. Lever the upper part off the lower part.
- 3. Cut the cable tie.
- You have removed the strain relief housing.