Intended use
The device is intended for use as a control system for automation, visualization and communication in machine and system engineering.
The device has been developed for an IP20 working environment. This involves finger protection and protection against solid foreign objects up to 12.5 mm. There is no protection against water. Operation of the devices in wet and dusty environments is not permitted.
The specified limits for technical data must be adhered to.
The device can be used within the documented operating conditions.
Potentially hazardous area
This device is only suitable for the following hazardous areas:
- For Zone 2 where gas is present as a combustible material. Zone 2 means that the environment is usually either not explosive or only for a short period of time.
Potentially hazardous area
The industrial PC is only suitable for the following hazardous areas:
- For Zone 2 where gas is present as a combustible material. Zone 2 means that the environment is usually either not explosive or only for a short period of time.
- For Zone 22 where dust is present as a combustible material. Zone 22 means that the surrounding area in the form of a cloud is either not at risk of explosion or only for a short period of time.
The device must be installed in a housing with IP54 protection rating for gas in accordance with EN 60079-7 or IEC 60079-7. A housing unit with an IP54 protection rating is required for fibers and lint as well as for non-conductive dust. IP6x protection rating is required for conductive dust in accordance with EN 60079-31 or IEC 60079-31.
Improper use
Do not use the device outside the documented operating conditions.
The device is not suitable for use in the following environments:
- The device may only be used in Zone 2 environments.
- The device is not suitable for use in aggressive environments, for example with aggressive gases or chemicals.
- The device is not suitable for residential areas. Relevant standards regarding interference emissions must be observed. The device must be installed in a housing or a control cabinet with suitable shielding.