Power supply

The industrial PC is supplied with a nominal voltage of 24 V. The 2x2-pin voltage socket (X101) is used for connection to the power supply and the external wiring of the industrial PC. The main supply voltage is applied between PIN 3 (0 V) and PIN 4 (24 V) of the socket.

Power supply 1:
Fig.2: Voltage socket pin numbering
Voltage socket pin assignment

Pin

Signal

Description

1

PC-ON

Input PC-ON

2

P-S

Power status output

3

GND

0 V

4

24 V

Power supply

The plug for the power supply is specified for 8 A and can accommodate wire cross-sections of up to 1.5 mm2. For long supply lines, use 1.5 mm2 cables to achieve a low voltage drop on the supply lines. There should be at least 22 V at the power supply plug of the industrial PC, so that the industrial PC remains switched on during voltage fluctuations. The plug is included in the delivery. You can obtain a replacement plug from your Beckhoff Sales using the following ordering option:

A maximum cable length of 30 m is permissible for the Power Status output.