Disconnecting the power supply and cables
CAUTION | |
Risk of electric shock Disconnecting the industrial PC during a thunderstorm can lead to electric shock.
|
Before you remove the industrial PC from the control cabinet, you must disconnect the cables and the power supply. Follow the steps below:
- 1. Shut down the industrial PC.
- 2. Disconnect the PC from your external 24 V power supply.
- 3. Unscrew the four-pin power supply connector and pull it out of the PC.
- 4. Remove the power supply cable if the four-pin connector is to remain with the PC.
- 5. Make a note of the wiring of all data transmission cables if you want to restore the cabling with another device.
- 6. Disconnect all data transfer cables from the industrial PC.
- 7. Finally, disconnect the ground connection.
- You have disconnected the cables and the power supply.