Power supply
The industrial PC is supplied with a nominal voltage of 24 V. The 2x2-pin voltage socket (X101) is used for connection to the power supply and the external wiring of the industrial PC. The main supply voltage is applied between PIN 3 (24 V) and PIN 4 (0 V) of the socket.
Pin | Signal | Description |
|---|---|---|
1 | PC-ON | Input PC-ON |
2 | P-S | Power status output |
3 | 24 V | Power supply |
4 | GND | 0 V |
The plug for the power supply is specified for 8 A and can accommodate wire cross-sections of up to 1.5 mm2. For long supply lines, use 1.5 mm2 cables to achieve a low voltage drop on the supply lines. There should be at least 22 V at the power supply plug of the industrial PC, so that the industrial PC remains switched on during voltage fluctuations. The plug is included in the delivery. You can obtain a replacement plug from your Beckhoff Sales using the following ordering option:
- C9900-P943: power supply connector for C60xx Industrial PC