Firmware-Update BX9000
Firmware update via Ethernet
The TwinCAT System Manager can be used to load new firmware to the BX9000 via Ethernet. Requirements:
TwinCAT 2.10 build 1251
BX9000 firmware 1.07 or above
Working Ethernet connection (from the PC to the BX9000).
Before you update the BX9000, delete the boot project and start the BX9000 without a PLC program.
Switch TwinCAT to Config mode and add a virtual Ethernet interface as a device.
Then insert the BX9000 and set the IP address.
The next step is to click the BX9000 with the right mouse button, and select the Firmware update via ADS function.
Then select the appropriate firmware. The update is automatic. The BX9000 will restart automatically when the update is complete.