ADS connection via serial interface
(from firmware version 1.xx or 0.99x, Bus Terminal Controllers of the BX series and for all BCxx50)
From TwinCAT 2.9 build 1020 (TwnCAT level PLC, NC or NCI)
|  | Use only a serial connection To ensure trouble-free operation of the ADS link via the serial interface, only a serial connection to the BX controller is allowed.  | 
|  | AMS Net ID in delivery state (default) For BX9000 The default AMS Net ID is 172.16.21.20.1.1. If the IP address of the BX9000 is changed, the AMS Net ID of the BX9000 also changes. There is a menu option for displaying the current AMS Net ID. For BC9050, BC9020, BC9120 The default AMS Net ID is 172.16.xxx.[DIP switch].1.1. If the IP address of the BX9xxx is changed, the AMS Net ID of the BX9xxx also changes. | 
Initializing the ADS connection
Enter the Bus Terminal Controller in the remote connection under TwinCAT. Click on the TwinCAT icon and open the features menu. The following settings can be made under the >AMS Remote< tab.

Remote Name: Any
AMS-Net-ID: 1.1.1.1.1.1 (Default)
Address: COM Port: Baud rate, parity, data bits, stop bits
Transport: Select "COM port"
When the Bus Terminal Controller is switched on, the default AMS Net ID is always "1.1.1.1.1.1" (except all Ethernet Controllers).
The AMS Net ID can be changed as required. Please note that the new AMS Net ID cannot be changed again in this way.
If you need to change the new AMS Net ID again, you have to restart the Bus Terminal Controller, so that the AMS Net ID is reset to the default AMS Net ID, "1.1.1.1.1.1".
You can now change the AMS Net ID again.
|  | Strings can only be entered at the second call No strings can be entered under address when the dialog is first called (see above). Enter the name, AMS Net ID and transport type and close the dialog. With the second call you can enter your COM port. | 
The communication starts when TwinCAT is in Config mode (TwinCAT icon is blue) or RUN mode (TwinCAT icon is green). The COM interface remains open until a TwinCAT stop occurs (TwinCAT icon is red). It is then available again for other programs. No error message is issued if the COM interface is used by another program during a TwinCAT restart (e.g. by the KS2000 configuration software).
|  | AMS Net ID after ADS connection via the fieldbus If you have addressed the Bus Terminal Controller with an ADS connection via the fieldbus before the serial ADS was used, the AMS Net ID was automatically changed by the System Manager. In this case a new serial ADS connection is only possible, if the AMS Net ID is adjusted. | 
BX series: reading the AMS Net ID
The current AMS Net ID can be read from the menu via the display of BX series Bus Terminal Controller.
| 
                    AMS | AMS Net ID |