General operating conditions

The following conditions must be met in order to ensure flawless operation of the fieldbus components.

Environmental conditions

Operation

The components may not be used without additional protection in the following locations:

Condition

Permissible range

Permissible ambient temperature during operation

See technical data

Permissible ambient temperature during operation

-25°C ... +85 °C

Installation position

variable

Vibration resistance

conforms to EN 60068-2-6 

Shock resistance

conforms to EN 60068-2-27, EN 60068-2-29

EMC immunity

conforms to EN 61000-6-2

Emission

conforms to EN 61000-6-4

Transport and storage

Condition

Permissible range

Permissible ambient temperature during storage

-25°C... +85 °C

Relative humidity

95 %, no condensation

Free fall

up to 1 m in the original packaging

Protection classes and types

Condition

Permissible range

Protection class in accordance with IEC 536 (VDE 0106, Part 1)

A protective conductor connection to the profile rail is necessary!

Protection class conforms to IEC 529

IP20 (protection against contact with a standard test finger)

Protection against foreign objects

Less than 12 mm in diameter

Protection against water

no protection

Component identification

Every supplied component includes an adhesive label providing information about the product's approvals.

General operating conditions 1:
Name plate of a BX controller

The following information is printed on the label:

Printed item

Meaning for this label

Precise product identification

BX model

Supply voltage Us

24 VDC (Use a 4 A fuse or a Class 2 power supply to meet UL requirements!)

Manufacturer

Beckhoff Automation GmbH

CE mark

Conformity mark

UL mark

General operating conditions 2:

Mark for UL approval. UL stands for the Underwriters Laboratories Inc., the leading certification organization for North America, based in the USA.
C = Canada, US = USA,
UL file number: E172151

Production identification

Serial No.: Serial number
HW: hardware version
Date: Date of manufacture
optional for BX9000 MAC-ID only