Slave address
Use the two rotary selection switches to set the slave address. The default setting is 11. All addresses from 0 to 63 are permitted. Each address may only occur once in the network. The address is edited when the BX Controller is switched off. The switches can be set to the required position using a screwdriver. Ensure that the switches engage correctly. The lower switch is the 10-multiplier, the upper switch is the 1-multiplier. The changed address is active as soon as the BX Controller is switched on again.

Example
You want to set address 34.
- lower rotary selection switch S311: 3
- upper rotary selection switch S310: 4