PROFIBUS address
The PROFIBUS address for the BX3100 can be set via two rotary selection switches. The default setting is 11. All addresses are permitted, although each address may only occur once within the network. For changing an address the Bus Coupler must be switched off. The switches can be set to the required position using a screwdriver. Ensure that the switches engage correctly. The lower switch is the 10-multiplier, the upper switch is the 1-multiplier. The address change becomes active when the BX3100 is switched on.
Sample
You want to set address 34.
- Lower rotary selection switch S311: 3
- Upper rotary selection switch S310: 4