COM port function block
COM Port Open
![](Images/gif/3207633547__Web.gif)
FUNCTION_BLOCK FB_COMPORTOPEN
VAR_INPUT
bOpen :BOOL;
stComConfig :ST_COMCONFIG;
VAR_OUTPUT
bBusy :BOOL;
bErr :BOOL;
iErrId :WORD;
iHandle :WORD;
Legend
bBusy: The function block is active as long it is TRUE.
bErr: Error bit.
iErrId: Error number.
iHandle: pointer transfer.
Return parameter iErrId |
Meaning |
---|---|
0 |
No error |
-1, 0xFFFF |
Incorrect COM port |
-2, 0xFFFE |
Incorrect or unsupported baud rate. Check the parameter stComConfig.BaudRate. |
-3, 0xFFFD |
Incorrect data format. Check the parameter stComConfig. |
-4, 0xFFFC |
Incorrect initialization of the COM interface |
-5, 0xFFFB |
Unsupported instance |
-6, 0xFFFA |
Incorrect size of the RX buffer |
-7, 0xFFF9 |
Incorrect size of the TX buffer |
-8, 0xFFF8 |
COM port is blocked |
COM Port Close
![COM port function block 1:](Images/gif/3207635979__Web.gif)
FUNCTION_BLOCK FB_COMPORTCLOSE
VAR_INPUT
bOpen :BOOL;
iHandle :WORD;
Legend
bClose: rising edge starts the function block
iHandle: pointer transfer of FB_COMPORTOPEN.
VAR_OUTPUT
bBusy :BOOL;
bErr :BOOL;
iErrId :WORD;
Legend
bBusy: The function block is active as long it is TRUE.
bErr: Error bit.
iErrId: Error number.
Return parameter iErrId |
Meaning |
---|---|
0 |
No error |
> 0 |
error number (#not documented#) |