Deactivating the LED for cycle time exceeding

The BX controller monitors the set task cycle time. If it is exceeded, the cycleTimeExceeded bit and the red PLC LED are set. In some applications the value may be exceeded for short periods, which is tolerable. This may be the case when many data are received in serial communication, for example. In order to avoid flickering of the red PLC LED, it can be switched off via ADSWRITE.

Structure of the ADSWRITE command

This ADSWRITE command enables the red PLC LED of the BX controller to be deactivated.

Input parameters

Description

NETID

local NetId of BX

Port number

800

IDXGRP

16#0000_4080

IDXOFFS

0

LEN

1 bytes

SRCADDR

Pointer on 1 bytes
0: red LED ON
1: red LED OFF