Star Hub (Multiport Tap)
Shorter drop line lengths must be maintained when passive distributors ("multiport taps"), such as the Beckhoff ZS5052-4500 Distributor Box. The following table indicates the maximum drop line lengths and the maximum length of the trunk line (without the drop lines):
| 
                   Baud rate  | 
                   Drop line length with multiport topology  | 
                   Trunk line length (without drop lines)  | 
|---|---|---|
| 
                   1 Mbit/s  | 
                   < 0,3 m  | 
                   < 25 m  | 
| 
                   500 kbit/s  | 
                   < 1,2 m  | 
                   < 66 m  | 
| 
                   250 kbit/s  | 
                   < 2,4 m  | 
                   < 120 m  | 
| 
                   125 kbit/s  | 
                   < 4,8 m  | 
                   < 310 m  |