BK9500 - Bus Coupler for USB

Address selection

Although it is the nature of the USB not to require address setting in the conventional sense, an address switch has nevertheless been integrated. This makes it possible to distinguish multiple Bus Couplers in one USB network.

The address is set by means of the DIP switch. Addresses from 0 to 127 are permitted.

 
 bk9500 adr
DIP switch

Priority of the address - example

DIP switch
 
Switch no.
1
2
3
4
5
6
7
8
 
Valence
20
21
22
23
24
25
26
27
 
Decimal
1
2
4
8
16
32
64
128
 
In this example
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
 
Example value
1
2
0
0
0
32
0
0
Total=35

Address in the TwinCAT System Manager

 
 BK9500_SystemManager_Address
Address in the TwinCAT System Manager

Enter the address that has been set using the DIP switch for each USB coupler into the TwinCAT System Manager. In an automatic device search, the TwinCAT System Manager will automatically determine the addresses that have been set for all the connected USB couplers.