Configuration with KS2000

The KS2000 configuration software (from version 3.2.8) can be used to set the TCP/IP address in a dialog box, or it can be written directly into the registers. DIP switches 9 and 10 (for BK9050 DIP switches 1 and 2 in blue) should both be OFF (0) before switching on.

Table 100

Register

High-Byte

Low-Byte

0

IP-Byte 2

IP-Byte 1

1

Not used

IP-Byte 3

Default

Byte

Default value (hex)

Default value (dec)

1

0xAC

172dec

2

0x10

16dec

3

0x11

17dec

4

(DIP switch)

(0 to 255dec)

Sample

Configuration with KS2000 1:
DIP switch

Switch no.

1

2

3

4

5

6

7

8

9

10

 

Valence

1

2

4

8

16

32

64

128

-

-

 

In this example

ON

OFF

OFF

ON

OFF

OFF

ON

ON

OFF

OFF

 

Value

1

0

0

8

0

0

64

128

-

-

Total=201

Configuration with KS2000 2:

Software reset

A software reset is required to save changes in the Bus Coupler tables. A hardware reset (power on/off) is not sufficient!