Configuration with KS2000
The KS2000 configuration software (from version 3.2.8) can be used to set the TCP/IP address in a dialog box, or it can be written directly into the registers. DIP switches 9 and 10 (for BK9050 DIP switches 1 and 2 in blue) should both be OFF (0) before switching on.
Table 100
|
Register |
High-Byte |
Low-Byte |
|---|---|---|
|
0 |
IP-Byte 2 |
IP-Byte 1 |
|
1 |
Not used |
IP-Byte 3 |
Default
|
Byte |
Default value (hex) |
Default value (dec) |
|---|---|---|
|
1 |
0xAC |
172dec |
|
2 |
0x10 |
16dec |
|
3 |
0x11 |
17dec |
|
4 |
(DIP switch) |
(0 to 255dec) |
Sample

Switch no. | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 |
|
Valence | 1 | 2 | 4 | 8 | 16 | 32 | 64 | 128 | - | - |
|
In this example | ON | OFF | OFF | ON | OFF | OFF | ON | ON | OFF | OFF |
|
Value | 1 | 0 | 0 | 8 | 0 | 0 | 64 | 128 | - | - | Total=201 |
![]() | Software reset A software reset is required to save changes in the Bus Coupler tables. A hardware reset (power on/off) is not sufficient! |