ADS Process Image
The process image of the Bus Terminals is sub-divided into input image and output image. The Bus Coupler first maps all complex (byte-oriented) Bus Terminals into the process image in the order in which they are inserted, and only at the end attaches the digital Bus Terminals to the process image.
The complex (byte-oriented) Bus Terminals are mapped as follows:
- Complete evaluation
- Word alignment
- Intel format
Sample 1
BK9000
4 x KL1xx4
2 x KL2xx2
1 x KL9010
|
Pos. |
Bus Terminal |
Input %I.. |
Output %Q.. |
|---|---|---|---|
|
1 |
KL1xx4 |
0.0 ... 0.3 |
- |
|
2 |
KL1xx4 |
0.4 ... 0.7 |
- |
|
3 |
KL1xx4 |
1.0 ... 1.3 |
- |
|
4 |
KL1xx4 |
1.4 ... 1.7 |
- |
|
5 |
KL2xx2 |
- |
0.0 ... 0.1 |
|
6 |
KL2xx2 |
- |
0.2 ... 0.3 |
|
9 |
KL6010 |
- |
- |
Sample 2
BK9000
4 x KL1xx4
2 x KL2xx2
1 x KL1501
1 x KL3xx2
1 x KL4xx2
1 x KL9010
|
Pos. |
Bus Terminal |
Input %I.. |
Output %Q.. |
|---|---|---|---|
|
1 |
KL1501 |
0..5 |
0..5 |
|
2 |
KL3xx2 |
6..13 |
6..13 |
|
3 |
KL4xx2 |
14..21 |
14..21 |
|
4 |
KL1xx4 |
22.0..22.3 |
- |
|
5 |
KL1xx4 |
22.4..22.7 |
- |
|
6 |
KL1xx4 |
23.0..23.3 |
- |
|
7 |
KL1xx4 |
23.4..23.7 |
- |
|
8 |
KL2xx2 |
- |
22.0...22.1 |
|
9 |
KL2xx2 |
- |
22.2...22.3 |
|
10 |
KL6010 |
- |
- |