LED displays

Module Status MS

LED

 

Meaning

RUN

green LED blinks

Configuration is incorrect

green LED is steadily lit

Status is OK

OVERFL

red LED blinks

K-bus error

red LED is steadily lit

Receive queue overflow

Network Status NS

LED

 

Meaning

CONNECT

green LED blinks

Bus Coupler is ready for communication, but not yet assigned to the master

BUS OFF

green LED is steadily lit

Bus Coupler is assigned to the master, data is being exchanged

red LED blinks

Timeout on I/O connection

red LED is steadily lit

BUS OFF: CAN error, devices have identical node address

I/O Status

LED

 

Meaning

I/O RUN

green LED is lit

The Bus Terminals are working correctly

I/O ERR

red LED is lit

I/O error, a Bus Terminal or an internal K-bus with a fault

I/O ERR

red LED blinks

The Bus Terminals are being configured