Module Assignment

The multi-configuration mode is possible with a maximum of 128 modules (terminals, IE modules, etc.). The specification of which of the modules configured in the CfgData are indeed inserted can be written with DPV1 Write and read with DPV1 Read.

Slot number

Index 

Length

Data  

Description  

0

1

1-15

Byte 0 (bit 0,1)

Assignment of module 1
0: DP DataExchange (default)
2: disabled (configured module missing)

Byte 0 (bit 2,3)

Assignment of module 2
0: DP DataExchange (default)
2: disabled (configured module missing)

Byte 0 (bit 4,5)

Assignment of module 3
0: DP DataExchange (default)
2: disabled (configured module missing)

Byte 0 (bit 6,7)

Assignment of module 4
0: DP DataExchange (default)
2: disabled (configured module missing)

Byte 1 (bit 0,1)

Assignment of module 5
0: DP DataExchange (default)
2: disabled (configured module missing)

...

 

Byte 15 (bit 6,7)

Assignment of module 64
0: DP DataExchange (default)
2: disabled (configured module missing)

2

1-15

Byte 0 (bit 0,1)

Assignment of module 65
0: DP DataExchange (default)
2: disabled (configured module missing)

Byte 0 (bit 2,3)

Assignment of module 66
0: DP DataExchange (default)
2: disabled (configured module missing)

Byte 0 (bit 4,5)

Assignment of module 67
0: DP DataExchange (default)
2: disabled (configured module missing)

Byte 0 (bit 6,7)

Assignment of module 68
0: DP DataExchange (default)
2: disabled (configured module missing)

Byte 1 (bit 0,1)

Assignment of module 69
0: DP DataExchange (default)
2: disabled (configured module missing)

...

 

Byte 15 (bit 6.7)

Assignment of module 128
0: DP DataExchange (default)
2: disabled (configured module missing)