Overview

Configuration types

The BC9191 Bus Terminal Controllers can be configured in two different ways: DEFAULT CONFIG or TwinCAT CONFIG.

DEFAULT-CONFIG

Fixed addressing BC9191 in the DEFAULT CONFIG:

input/output

Designation

Address

Data type

Digital_Input_1

DI 1

IX 30.0

Bool

Digital_Input_12

DI 2

IX 30.1

Bool

Digital_Input_3

DI 3

IX 30.2

Bool

Analog_PT_1000

PT 1000

IW 2

Integer

Analog_Setpoint

Setpoint

IW 6

Integer

Analog_Input_1

AI 1

IW 10

Integer

Analog_Input_2

AI 2

IW 14

Integer

Analog_Input_3

AI 3

IW 18

Integer

Analog_Output_1

AO 1

QW22

Integer

Analog_Output_2

AO 2

QW26

Integer

Digital_LED_Output

DO 1

QX 30.0

Bool

Relay_Output_2KW

2 kW2

QX 30.1

Bool

Relay_FAN_1

FAN 1

QX 30.2

Bool

Relay_FAN_2

FAN 2

QX 30.3

Bool

Relay_FAN_3

FAN 3

QX 30.4

Bool

TRIAC_Y1_Output

Y1

QX 30.5

Bool

TRIAC_Y2_Output

Y2

QX 30.6

Bool

KL6581.InData

CAN

IB32 … IB43

12 bytes

KL6581.OutData

CAN

QB32 … QB43

12 bytes

Further connected terminals start with the addresses IB44 or Qb44

Fixed addressing BC9191-0100 in the DEFAULT-CONFIG:

input/output

Designation

Address

Data type

Digital_Input_1

DI 1

IX 30.0

Bool

Digital_Input_12

DI 2

IX 30.1

Bool

Digital_Input_3

DI 3

IX 30.2

Bool

Analog_PT_1000

PT 1000

IW 2

Integer

Analog_Setpoint

Setpoint

IW 6

Integer

Analog_Input_1

AI 1

IW 10

Integer

Analog_Input_2

AI 2

IW 14

Integer

Analog_Input_3

AI 3

IW 18

Integer

Analog_Output_1

AO 1

QW22

Integer

Analog_Output_2

AO 2

QW26

Integer

Digital_LED_Output

DO 1

QX 30.0

Bool

Relay_Output_2KW

2 kW2

QX 30.1

Bool

Relay_FAN_1

FAN 1

QX 30.2

Bool

Relay_FAN_2

FAN 2

QX 30.3

Bool

Relay_FAN_3

FAN 3

QX 30.4

Bool

TRIAC_Y1_Output

Y1

QX 30.5

Bool

TRIAC_Y2_Output

Y2

QX 30.6

Bool

KL6041.InData

RS 485

IB32 … IB55

23 bytes

KL6041.OutData

RS 485

QB32 … QB55

23 bytes

Further connected terminals start with the addresses IB 56 or QB 56

TWINCAT-CONFIG

In the TWINCAT CONFIG the integrated inputs/outputs and connected Bus Terminals can be freely linked (TwinCAT System Manager file required). The configuration is transferred to the BC9191 with the System Manager via ADS.

For the TwinCAT Config (TC file) you need a PC with TwinCAT 2.10 build 1322 or higher.

OThe System Manager of the TwinCAT 2 program can be used to parameterize the following properties:

The configuration can be transferred to the BCx9191 via ADS protocol.

The TwinCAT configuration can be used to link variables, I/Os and data.

In addition, the TwinCAT configuration can be used to parameterize special behavior, for example whether data are preserved or set to "0" in the event of an FK-Bus error.
The internal clock of the BC9191 can be set via a tab in the System Manager.