Configuration with KS2000
Using the KS2000 configuration software (as from version 3.2.8) you can set the TCP/IP address via a dialog box or write directly into the registers. DIP switches 1 and 2 in blue should both be OFF (0) before switching on.
In the KS2000 dialog box it is possible to:
- change the name of the controller
- change the first three bytes of the IP address The last byte of the IP address is defined by DIP switches 1 to 8.
- change the settings of subnet mask, default gateway and DNS server.

Table 100
Register |
High byte |
Low byte |
---|---|---|
0 |
IP-Byte 2 |
IP-Byte 1 |
1 |
Not used |
IP-Byte 3 |
Default
Byte |
Default value (hex) |
Default value (dec) |
---|---|---|
1 |
0xAC |
172dec |
2 |
0x10 |
16dec |
3 |
0x11 |
17dez |
4 |
(DIP switch) |
(0 to 255dec) |