ADS Process Image
16 bytes input and output are assigned to the fieldbus by default in all the BCxxxx devices. These variables are known as PLC variables, and are located, under the BCxxxx default setting, starting from address 128 in the process image. The setting can be made with the KS2000 configuration software, or, for some BCs that support ADS, can be changed by means of start-up parameters.