Preset single register (Function 6)

The function Preset singles register can be used to access the output or flag process image (only for controllers) and the Modbus TCP interface.

Function 6 writes the first output word. The outputs start at an offset of 0x0800. Here again the offset always describes a word. This means offset 0x0803 refers to the fourth word in the output process image.

Query

Byte name

Sample

Function code

6

Start address high

8

Start address low

0

Data high

63

Data low

255

The Fieldbus Coupler replies with the same telegram and confirmation of the received value.

Response

Byte name

Sample

Function code

6

Start address high

8

Start address low

0

Data high

63

Data low

255