Reaction times

BC9000 reaction time

ADS

Time [ms]

TCP

23 to 50 ms + task time on the BC9000 (jitter)

UDP

2 to 3 ms + task time on the BC9000 (jitter)

 

Modbus

Time [ms]

TCP

12 to 15 ms + task time on the BC9000 (jitter) (default)

Fast TCP*

1 to 3 ms + task time on the BC9000 (jitter)

* as from firmware B7, Table 100, Register 29 - "1" Fast TCP / "0" TCP (see Modbus Interface)

BK9000 reaction time

ADS

Time [ms]

TCP

23 to 50 ms

UDP

2 to 3 ms

 

RT-Ethernet**

Time [ms]

RAW

< 1 ms + K-bus (depending on the K-bus propagation delay)

 

Modbus

Time [ms]

TCP

12 to 15 ms (default)

Fast TCP*

1 to 3 ms

* as from firmware B5, Table 100 Register 29 - "1" Fast TCP / "0" TCP (see Modbus interface)** from firmware B8