KS8000 Process Image
Default config (without TwinCAT System Manager):
The data of the KS8000 slave interface are stored in the allocated section of the BC8x50.
The input data from the master perspective are stored in the controller output section from address %QB1000 (address offset 0 from the master perspective).
The output data from the master perspective are stored in the controller input section from address %IB1000 (address offset 0 from the master perspective).
The maximum data length is 512 bytes input and 512 bytes output.