Allocated flags
4 kbyte of allocated flags are available. They can be used to assign different variable types to the same address, e.g. for converting strings to bytes. Data can also be placed here that can be read or written via ADS by the controller.
Allocated variables are not remanent data For the Bus Terminal Controllers of the BX series and the BCxx50 the allocated variables are not saved as remanent data. |
Reading/writing of allocated flags via ADS
The flags may also be read via the controller and ADS. In PROFIBUS, the DPV-1 services are used for this purpose, in CANopen SDO communication is used.
The AmsNetID can be obtained from the System Manager, or it can be displayed via the Bus Terminal Controller menu.
The PLC port number is 800.
Index group |
Meaning |
Index offset (value range) |
---|---|---|
0x4020 |
Flag (only BXxxx0) |
0..4096 |
Example
BX program
VAR
Flag_01 AT %MB0: WORD;
END_VAR
TwinCAT PC/CX master program
VAR
fbADRSREAD: ADSREAD;
Flag_M: WORD;
END_VAR
fbADRSREAD(
NETID:='172.16.3.0.2.3' , (* AMSNetId BX *)
PORT:=800 , (* 800 - PLC *)
IDXGRP:=16#4020 , (* 0x4020hex falgs *)
IDXOFFS:=0 , (* byte offset *)
LEN:=2 , (* Lenght byte *)
DESTADDR:=ADR(Merker) ,
READ:=TRUE ,
TMOUT:=t#1s );
IF NOT fbADRSREAD.BUSY THEN
fbADRSREAD(READ:=FALSE);
END_IF