Bus length
The maximum length of a CAN bus is primarily limited by the signal propagation delay. The multi-master bus access procedure (arbitration) requires signals to reach all the nodes at effectively the same time (before the sampling within a bit time). Since the signal propagation delays in the CAN connecting equipment (transceivers, optocouplers, CAN controllers) are almost constant, the line length must be chosen in accordance with the baud rate.
|
Baud rate | Bus length |
|---|---|
500 kbit/s | < 100 m |
250 kbit/s | < 250 m |
125 kbit/s | < 500 m |