738E, HpfDsl: Encoder file processing error, FileId=0xXX, Arg=0xXX

An error ocured during processing the encoder file.
FileId:
0x01 = Electronic Data Sheet File
0x02 = User Data File
0x03 = Position Offset File
0x04 = Commutation Offset File
0x05 = Cogging Compensation Coefficients File
Arg:
0x01 = No File Header Existing
0x02 = File Size Error
0x03 = File Size Not Aligned
0x04 = Invalid File Header Error 1
0x05 = Invalid File Header Error 2
0x06 = Invalid File Header Error 3
0x07 = Invalid File Header Crc1
0x08 = Invalid File Header Crc2
0x10 = Invalid Vendor Key

Diagnostic Code (Hex.)

Diagnostic Code (Dez.)

738E

29582

Class

Type

Error

Feedback error

Standard Reaction

Reset

Axis is inoperable

Execute Reset-Command (Fault reset).


Internal: 0x738E, HpfDsl: Encoder file processing error, FileId=0x%X, Arg=0x%X