7381, HpfDsl: Encoder shutdown failed, Id=0xXX, Arg=0xXX

The stop sequence of the encoder failed:

Id=0x01: Enocder stop failed with internal error (see 'Arg')
Id=0x02: Encoder stop failed. The link isn't down. (Arg=internal status)

Diagnostic Code (Hex.)

Diagnostic Code (Dez.)

7381

29569

Class

Type

Error

Feedback error

Standard Reaction

Reset

Axis is inoperable

Execute Reset-Command (Fault reset).


Internal: 0x7381, HpfDsl: Encoder shutdown failed, Id=0x%X, Arg=0x%X