8A81, Illegal Modes Of Operation change

The modes of operation was changed in an illegal transition while the axis was enabled.

Diagnostic Code (Hex.)

Diagnostic Code (Dez.)

8A81

35457

Class

Type

Error

Error

Standard Reaction

Reset

Closed loop ramp

Execute Reset-Command (Fault reset).

Possible Causes

Solutions

The modes of operation was changed in an illegal transition while the axis was enabled.

Please check the write operations to Object 0x6060 (Ch A) or Object 0x6860 (Ch B).


Internal: 0x8A81, Illegal Modes Of Operation change