639B, additional Factor Group Parameters: Position encoder resolution illegal motor revolutions
The actual combination of the factor group Parameters is not allowed for this Device.
Diagnostic Code (Hex.) |
Diagnostic Code (Dez.) |
---|---|
639B |
25499 |
Class |
Type |
---|---|
Error |
Error |
Standard Reaction |
Reset |
---|---|
Axis is inoperable |
Execute Reset-Command (Fault reset). |
Possible Causes |
Solutions |
---|---|
The additional position encoder resolution - motor revolutions contains an illegal value (Object 0x60EB/1 ChA or 0x68EB/1 ChB). |
Please compare it to your encoder values. |
Internal: 0x639B, additional Factor Group Parameters: Position encoder resolution illegal motor revolutions