2340, Short circuit (motor-side)

The drive hardware detected an over-current on the motor phases. The short circuit detection was triggered.

Diagnostic Code (Hex.)

Diagnostic Code (Dez.)

2340

9024

Class

Type

Error

Overcurrent error

Standard Reaction

Reset

Torque off

A fatal error occurred. A device reboot is required.

Possible Causes

Solutions

Short circuit in the motor cable.

Check the motor cable

Short circuit in the motor winding.

Check the motor winding with an high voltage test or check the winding resistance.


Internal: 0x2340, Short circuit (motor-side)