A003, Transition Pre-Op to Safe-Op not successful. Sync Manager Address Range overlap.

Diagnostic Code (Hex.)

Diagnostic Code (Dez.)

A003

40963

Class

Type

Error

Error

Standard Reaction

Reset

Axis is inoperable

Execute Reset-Command (Fault reset).

Possible Causes

Solutions

The Parameters of the CoE Communication Objects do not fit the Sync Manager Parameters.

Please check, if you are working with the right EtherCAT Device Description XML-File.


Internal: 0xA003, Transition Pre-Op to Safe-Op not successful. Sync Manager %u Address Range 0x%x..0x%x overlaps Sync Manager %u Address Range 0x%x..0x%x