3130, Mains phase failure

One phase has failed in the 3-phase supply.

Diagnostic Code (Hex.)

Diagnostic Code (Dez.)

3130

12592

Class

Type

Error

Error

Standard Reaction

Reset

NC-Handling order

Execute Reset-Command (Fault reset).

Possible Causes

Solutions

The mains voltage supply is faulty.

Analyze the mains voltage supply.

You have connected a singe-phase mains supply but parameterized three phases.

Check and adjust the mains type parameterization. Switch the mains voltage off and on again.

The mains voltage supply is repeatedly exposed to interference.

Try to use a mains filter.


Internal: 0x3130, Mains phase failure