7182, Wrong xml file

Device description file does not match to device or to firmware.

Diagnostic Code (Hex.)

Diagnostic Code (Dez.)

7182

29058

Class

Type

Error

Error

Standard Reaction

Reset

PSM is not ready to operate and transition PREOP to SAFEOP disabled

A reset is not possible. The PSM detected a fatal hard- or software error.

Possible Causes

Solutions

Wrong file by firmware update choosen.

Start again a firmware update with the right file.

The firmware or device description files do not match to device.

Check the files. Change them or change the device, if necesary.

Wrong file by device description update choosen.

Start again a firmware update with the right file. A separate device description update is not necessary because this is made automatically by a firmware update.