3110, Mains over-voltage

The actual mains voltage exceeds the parametrized mains voltage (0x8000:06) by more than 20% or by more than the parametrized positive tolerance (0x8000:07), if this higher than 20%.

Diagnostic Code (Hex.)

Diagnostic Code (Dez.)

3110

12560

Class

Type

Error

Error

Standard Reaction

Reset

NC-Handling order

Execute Reset-Command (Fault reset).

Possible Causes

Solutions

The actual mains voltage is too high.

Look for a allowed mains voltage.

The positive mains voltage tolerance (0x8000:07) is parametrized too low.

Correct this parametrized value.