7112, Over current brake chopper, Operating time counter: UU s., Entry counter: UU
Your connected brake resistor (internal or external) was overloaded.
Diagnostic Code (Hex.) |
Diagnostic Code (Dez.) |
---|---|
7112 |
28946 |
Class |
Type |
---|---|
Error |
Error |
Standard Reaction |
Reset |
---|---|
Brake chopper is disabled |
A reset is not possible. The PSM detected a fatal hard- or software error. |
Possible Causes |
Solutions |
---|---|
Current at connected brake resistor is too high. The brake resistor may be damaged. |
Switch off the mains voltage and the 24V-supply. Check whether your brake resistor is damaged, if external one connected. Try to operate power supply module again. If this error happens repeatedly, please contact your competent Beckhoff office. |
Your applikation is so designed, that this exceeds the maximal allowed current at the brake resistor. |
Analize your application and make that this overcurrent does not happen. |
Internal: 0x7112, Over current brake chopper, Operating time counter: %u s., Entry counter: %u