Firmware downgrade | Firmware version V1.07 or higher to (V1.03–V1.06)

Firmware downgrade | Firmware version V1.07 or higher to (V1.03–V1.06) 1:

Do not perform firmware updates during operation

Firmware updates must not be performed while a machine is in operation. The update can be performed in configuration mode or in TwinCAT Run Mode. If the machine is in Run Mode, make sure that the axis on which the firmware update is being performed is disabled.

Firmware downgrade | Firmware version V1.07 or higher to (V1.03–V1.06) 2:

Downgrade process

A separate bootloader downgrade process is not necessary for the firmware downgrade procedure from V1.07 or higher to (V1.06–V1.03).

 

AX8000 firmware downgrade from V1.07 or higher to (V1.06–V1.03)

Firmware downgrade | Firmware version V1.07 or higher to (V1.03–V1.06) 3:
►Request device's EtherCAT state [bootstrap]
Firmware downgrade | Firmware version V1.07 or higher to (V1.03–V1.06) 4:
►Download the required firmware version via (FoE) download
Firmware downgrade | Firmware version V1.07 or higher to (V1.03–V1.06) 5:
►Confirm with OK
Firmware downgrade | Firmware version V1.07 or higher to (V1.03–V1.06) 6:

You do not need to enter a password.

Firmware downgrade | Firmware version V1.07 or higher to (V1.03–V1.06) 7:
►Perform a Power cycle

 

 

 

 

 

Completed firmware downgrade

 

The EtherCAT revision states the minimum firmware version required for the current configuration. If the firmware is lower than the firmware associated with the EtherCAT revision, the device cannot be operated.

 

Conditions for operation

Firmware version ≥ reference firmware version for the
EtherCAT revision