Supply networks

The Multi-axis servo system AX8000 is suitable for operation on grounded single-phase or three-phase networks. The respective network configurations differ by the type of ground connection. For a better understanding, the table below contains examples with the associated meaning:

Network configuration

French term

Meaning

TN

Terre Neutre

Neutral grounding of a point

  TN-C

Terre Neutre Combiné

Combined neutral grounding:

Neutral conductor and protective conductor combined to form PEN conductor

  TN-S

Terre Neutre Combiné Séparé

Separate neutral grounding:

Separate neutral conductor and protective conductor

TT

Terre Terre

Direct grounding of a point

IT

Isolé Terre

Isolation of all active parts from grounding

 

Connection to TN systems (including the TN-C and TN-S variants) and TT systems is possible without any additional measures.

For all other networks, operation is only possible on isolating transformers. An isolating transformer is a mains transformer that transfers the mains voltage to the secondary winding via an electrical isolation. A star point grounded network is made available with the help of this protective isolation.

 

The AX8000 power supply modules are equipped with a wide-range voltage input on terminal point X01 and can be connected to the following voltage systems: